TP-P 400

Standby Power

400 kVA

Prime Power

360 kVA

Back
TP-P 400
TURQPOWER

TP-P 400

Perkins Constructed to high industrial standards, this professional engine generator system operates with full stability in both automatic and manual scenarios.

Power (Prp / Esp):

360 / 400 kVA

(288 / 320 kW)

RPM

Speed / Frequency:

1500 Rpm / 50 Hz

Version:

Industrial

V

Voltage:

231 / 400

CE declaration of conformity

Stand By Rating (ESP)

Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528. Overload is not allowed.

Prime Rating (PRP)

Applicable for supplying power to varying electrical load for unlimited hours. Prime Power is in accordance with ISO 8528. Ten percent overload capability is available in accordance with ISO 3046.

Continuous Operation

Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous power is in accordance with ISO 8528. It is for projects where there is no main grid.

Technical Specifications

Engine Hardware Specifications

Engine brandPerkins
Engine model2206A-E13TAG2
Number of cylinders6 - Line
Cylinder volume12,5 lt
Bore x Stroke130 x 157 mm
Cooling systemLiquid (water + antifreeze)
Coolant capacity51 lt
Total oil capacity40 lt
Speed governorElectronic

Fuel Consumption Values

100% Load

71 lt/h

75% Load

54 lt/h

50% Load

37 lt/h

Physical Dimensions & Weights

Canopy Type

Dimensions (W x L x H)1550x4200x2300 mm
Weight3840 kg
Fuel Tank Capacity600 lt

Open Type (Without Canopy)

Dimensions (W x L x H)1550x3500x2025 mm
Weight3151 kg
Fuel Tank Capacity600 lt

Standard & Optional Equipments

Engine

Turqpower generator sets use leading engine brands that are compliant with ISO8528, ISO3046, BS 5514, DIN 6271 standards. These engines with low fuel consumption provide accurate speed setting.

Alternator

Our products prefer brands with high quality, efficiency and durability. Alternators meeting EC 60034-1, CEI EN 60034-1, BS 4999-5000 standards have maintenance-free bearing systems.

Cooling System

Consisting of a quality industrial-type radiator, expansion tank, and cooling fan, the system keeps the temperature of the generator set equipment constant at a stable level.

Chassis and Fuel Tank

The chassis is manufactured from steel with durability to carry the load of the generator set. Standard chassis and customized solutions designed in line with customer demands facilitate positioning.

Canopy Specifications

  • Noise emission compliant with 2000/14/EC directives
  • Lifting from 2 or 4 points depending on canopy size
  • Hidden exhaust system inside the canopy
  • Emergency stop button positioned on the canopy
  • Reinforced paint against corrosion and rust
  • Superior acoustic performance for sound insulation
  • Custom size and design options for customer demands

Optional Equipments

  • Medium voltage alternator & dual AVR / PMG
  • Remote monitoring systems
  • Automatic fuel filling system
  • Alternator, oil and fuel winding heaters
  • Synchronization systems
  • Custom insulated canopies and trailer
  • Seismic solutions and remote radiators

Operations Features (Option Features)

  • AREP
  • PMG
  • EBS
  • Air inlet filter
  • Louver (5% deration)
  • Space heater
  • Digital AVR
  • Severe environmental impregnation
  • Stator sensor
  • PT100
  • Rotor sensor
  • Double bearing
  • Drip proof cover
  • IP44 terminal cover
  • Double bearing

Radio interference suppression that meets or exceeds EU standard EN61000-6. Voltage regulation at steady state. Total waveform distortion at full load. Turqpower reserves the right to change product specifications without notice.

Digital controller (Datakom & ComAp)

Datakom D300
Datakom D300
Datakom D500
Datakom D500
ComAp AMF 25
ComAp AMF 25

Software features are equipped with easy firmware update via USB port. Windows-based PC software enables monitoring and programming via USB, RS-485, RS-232, Ethernet and GPRS. Web-based Scada service allows unlimited number of generator sets to be monitored from a single center.

Highlighted Main Features
Diesel and gas generator support
400Hz operation support
400 event logs, full snapshot
All parameters can be edited from front panel
3 level configuration password
128x64 graphical LCD display
Downloadable languages
V & I waveform display
V & I harmonic analysis
16Amp MCB & GCB outputs
8 configurable digital inputs
6 configurable digital outputs
3 configurable analog inputs
CANBUS-J1939 & MPU support
3 configurable service alarms
Multiple automatic test runs
Weekly schedule
Dual mutual standby (equal aging)
Fine speed adjustment on selected ECUs
Automatic fuel pump control
Disable protections feature
Excess power and reverse power protection
Overload IDMT protection
Load shedding and dummy load
Fuel filling and theft alarm
Real time clock with battery backup
Idle speed control
USB, RS-485, Ethernet and GPRS setup
Free configuration program
Allows SMS controls
Automatic GSM geolocation
IP65 protection (with optional gasket)
Communication & Modules
USB Device & J1939-CANBUS
Geolocation via GSM
Internet central monitoring
Sending SMS and E-mail
Rainbow Plus free PC software
Modbus RTU & TCP/IP
GSM Modem (2G-3G-4G)
Ethernet 100Mbps
Wi-Fi (802.11 b/g/n)
RS-485 and RS-232
Measurement & Functions
Mains & Generator voltages (PN/PP)
Mains & Generator frequency
Phase and neutral currents
Phase and total kW, kVA, kVAr, pf
Engine speed (RPM)
Battery voltage
AMF UnitRemote StartManual StartEngine Controller